Functional Statements

1) The objectives of this Code are achieved by measures, such as those described in the acceptable solutions in Division B, that are intended to allow the building or its elements to perform the following functions (see Appendix A):
F01 To minimize the risk of accidental ignition.
F02 To limit the severity and effects of fire or explosions.
F03 To retard the effects of fire on areas beyond its point of origin.
F04 To retard failure or collapse due to the effects of fire.
F05 To retard the effects of fire on emergency egress facilities.
F06 To retard the effects of fire on facilities for notification, suppression and emergency response.
F10 To facilitate the timely movement of persons to a safe place in an emergency.
F11 To notify persons, in a timely manner, of the need to take action in an emergency.
F12 To facilitate emergency response.
F13 To notify emergency responders, in a timely manner, of the need to take action in an emergency.
F20 To support and withstand expected loads and forces.
F21 To limit or accommodate dimensional change.
F22 To limit movement under expected loads and forces.
F23 To maintain equipment in place during structural movement.
F30 To minimize the risk of injury to persons as a result of tripping, slipping, falling, contact, drowning or collision.
F31 To minimize the risk of injury to persons as a result of contact with hot surfaces or substances.
F32 To minimize the risk of injury to persons as a result of contact with energized equipment.
F33 To limit the level of sound of a fire alarm system.
F34 To resist or discourage unwanted access or entry.
F35 To facilitate the identification of potential intruders.
F36 To minimize the risk that persons will be trapped in confined spaces.
F40 To limit the level of contaminants.
F41 To minimize the risk of generation of contaminants.
F42 To resist the entry of vermin and insects.
F43 To minimize the risk of release of hazardous substances.
F44 To limit the spread of hazardous substances beyond their point of release.
F46 To minimize the risk of contamination of potable water.
F50 To provide air suitable for breathing.
F51 To maintain appropriate air and surface temperatures.
F52 To maintain appropriate relative humidity.
F53 To maintain appropriate indoor/outdoor air pressure differences.
F54 To limit drafts.
F55 To resist the transfer of air through environmental separators.
F56 To limit the transmission of airborne sound into a dwelling unit from spaces elsewhere in the building (see Sentence 3.1.1.2.(2) for application limitation).
F60 To control the accumulation and pressure of water on and in the ground.
F61 To resist the ingress of precipitation, water or moisture from the exterior or from the ground.
F62 To facilitate the dissipation of water and moisture from the building.
F63 To limit moisture condensation.
F70 To provide potable water.
F71 To provide facilities for personal hygiene.
F72 To provide facilities for the sanitary disposal of human and domestic wastes.
F73 To facilitate access to and circulation in the building and its facilities by persons with physical or sensory limitations (see Sentence 3.1.1.2.(3) for application limitation).
F74 To facilitate the use of the building's facilities by persons with physical or sensory limitations (see Sentence 3.1.1.2.(3) for application limitation).
F80 To resist deterioration resulting from expected service conditions.
F81 To minimize the risk of malfunction, interference, damage, tampering, lack of use or misuse.
F82 To minimize the risk of inadequate performance due to improper maintenance or lack of maintenance.