9.10.14.4.(9)

Intent

Intent 1:

To exempt certain exposing building faces from the requirements of Sentence 9.10.14.4.(1), which would otherwise limit the area of unprotected openings, and permit unlimited unprotected openings, on the basis that the building face is readily accessible to firefighters [who will be able to effectively carry out fire suppression operations] and the limiting distance is not less than 9 m.