Intent 1:
To remove the requirement in Sentence 4.2.7.4.(1) for transfer and dispensing operations to be conducted in specially
equipped and protected rooms [conforming to Subsection 4.2.9.] provided:
- the operations are conducted in a storage area of limited
size, which would minimize the total fire load and thus not pose an
undue hazard to other parts of the building if involved in a fire,
and
- safety precautions are taken to limit the probability
that such operations will lead to a fire or explosion.