4.3.13.4.(2)

Intent

Intent 1:

To remove the requirement in Sentence 4.3.13.4.(1) for tanks to be located in a dedicated storage room if:

  • the tanks are located on the first storey where manual firefighting operations are not as likely to be delayed or impeded,
  • limited to only certain special process operations and quantities [quantities greater than those permitted in Sentences 4.2.8.2.(1) and (2) but not exceeding 50% of those permitted in Table 4.3.13.4.A. for a single class of liquid], and
  • the installation meets certain requirements [in conformance with Articles 4.3.13.9. to 4.3.13.12. and 4.3.14.4.].