4.8.9.2.(2)

Objective

OP3 Protection of Adjacent Buildings or Facilities from Fire

Attribution

Intent

Intent 1:

To supersede the requirements of Sentence 4.8.9.2.(1) and permit the installation of cargo pumps on piers or wharves of combustible construction if certain measures are taken [pumps are located in pump houses conforming to Subsection 4.8.10., and located not less than 3 m from other buildings].

This is to limit the probability that:

  • liquid spillage or leakage will not be contained, which could lead to the spread of liquid outside of the pump house and to adjacent buildings and facilities, which could lead to the ignition of vapour from a nearby ignition source, which could lead to damage to adjacent buildings and facilities,
  • a fire involving the pump house will spread to adjacent buildings and facilities, which could lead to damage to adjacent buildings and facilities, and
  • leakage or spillage from the pump operations will spread liquid to adjacent buildings and facilities, which could lead to the ignition of vapour from a nearby ignition source, which could lead to damage to adjacent buildings and facilities.

Top of Page