Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.1.7.5.(1)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Minimum fire-resistance rating of loadbearing walls, columns and arches in the storey immediately below a floor or roof assembly required to have a fire-resistance rating, in buildings described in Sentence 1.3.3.2.(1) of Division A, except as permitted by:
  • Sentence (2), which applies to walls, columns and arches supporting a service room or service space,
  • Articles 3.2.2.20. to 3.2.2.83. for mixed types of construction.
Top of Page
Intent
Intent 1: 
To limit the probability that such structures will have insufficient resistance to fire, which could lead to the collapse of the structures and their supported assemblies, which could lead to harm to persons.