Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.1.8.8.(1)
+
Application
Application 1: 
Fire dampers in noncombustible branch ducts that have a melting point above 760°C and that penetrate a required fire separation where the ducts:
  • serve only air-conditioning units or combined air-conditioning and heating units discharging air not more than 1.2 m above the floor and have a cross-sectional area not more than 0.013 m2, or
  • are connected to exhaust duct risers that are under negative pressure and in which the air flow is upward as required by Article 3.6.3.4. and are carried up inside the riser not less than 500 mm.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A.
Top of Page
Intent
Intent 1: 
To exempt certain branch ducts from the application of Sentence 3.1.8.7.(1), which would otherwise require fire dampers, on the basis that the lack of fire dampers in this case will not lead to significant spread of fire.
Intent 2: 
To direct Code users to Article 3.6.3.4. for exhaust duct risers referred to in Clause 3.1.8.8.(1)(b).