Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.1.8.12.(4)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Method of release of hold-open devices on doors in required fire separations and where a fire alarm system is provided.
Exceptions: 
except:
  • for hold-open devices on doors located between corridors used by the public and adjacent sleeping rooms in a hospital or nursing home,
  • for hold-open devices that are designed to release by heat-actuated devices in conformance with Sentence 3.1.8.12.(2),
  • as stated in Sentence 3.1.8.12.(1), which applies to exit doors in buildings more than 3 storeys in building height, and
  • as stated in Clause 3.3.5.7.(3)(c), which applies to doors for vestibules between storage garages and other parts of a building.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A, and to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9] as stated in Sentence 9.10.13.11.(1).
Top of Page
Intent
Intent 1: 
To limit the probability that a hold-open device will not release a door and maintain the integrity of the fire separation [in which the door is located] when the fire alarm system is actuated, which could lead to the spread of fire on the other side of the fire separation, which could lead to harm to persons.