Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.1.9.3.(2)
+
Application
Application 1: 
Totally enclosed non-metallic raceways conforming to Article 3.1.5.20., optical fibre cables, and electrical wires and cables, single or grouped, with combustible insulation, jackets or sheathes that conform to the requirements of Clause 3.1.5.18.(1)(a) and that are not installed in totally enclosed noncombustible raceways, which penetrate an assembly required to have a fire-resistance rating, and where the overall diameter of the single or grouped wires or cables, or the raceways is not more than 25 mm.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A.
Exceptions: 
except as stated in Sentence 3.1.9.3.(3), which applies to single conductor metal sheathed cables.
Top of Page
Intent
Intent 1: 
To exempt certain service equipment from the application of Sentence 3.1.9.2.(1) if certain conditions are met, on the basis that the equipment is deemed to insignificantly contribute to the growth and spread of fire.