Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.1.9.4.(2)
+
Application
Application 1: 
Combustible water distribution piping that has an outside diameter not more than 30 mm that penetrates a vertical fire separation that is required to have a fire-resistance rating, where the piping is sealed in conformance with Clause 3.1.9.1.(1)(a).
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A, and to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9] as stated in Sentence 9.10.9.6.(7).
Top of Page
Intent
Intent 1: 
To exempt certain piping from the application of Sentence 3.1.9.2.(1) if certain conditions are met, on the basis that the piping is deemed to insignificantly contribute to the growth and spread of fire.
Intent 2: 
To override the options offered in Sentence 3.1.9.1.(1) and force the use of Clause 3.1.9.1.(1)(a) for certain piping exempted from the application of Sentence 3.1.9.2.(1).