Warning This information has been archived because it is outdated and no longer relevant.

Archived Content

Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.1.11.3.(1)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Blocking off [fire stopping] between wood nailing elements of concealed spaces in which there is an exposed ceiling finish with a flame-spread rating more than 25.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A that are required to be of noncombustible construction.
Top of Page
Intent
Intent 1: 
To limit the probability that certain concealed spaces will not be separated from certain other parts of the building, which could lead to the spread of fire within these spaces, which could lead to harm to persons.
Intent 2: 
To limit the probability that fire stopping material used to block and separate concealed spaces will not remain in place for a certain minimum time when subjected to fire conditions, which could lead to the spread of fire within these spaces, which could lead to harm to persons.
Intent 3: 
To state the application of Article 3.1.11.7.
Top of Page