Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.1.13.6.(2)
+
Application
Application 1: 
Interior wall finish of corridors referred to in Sentence 3.1.13.6.(1), in buildings described in Sentence 1.3.3.2.(1) of Division A, where the flame-spread rating is not more than:
  • 25 on the upper half of the wall, and
  • 150 on the lower half of the wall.
Application 2: 
This also applies to occupancies in the corridor, as stated in Sentence 3.1.13.6.(4).
Top of Page
Intent
Intent 1: 
To exempt interior wall finishes in corridors from the application of Sentences 3.1.13.2.(1) and 3.1.13.6.(1), which would otherwise require certain maximum flame-spread ratings, if certain conditions are met, on the basis that these finishes will not significantly contribute to the spread of flame.