Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.1.13.6.(5)
OS1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Interior ceiling finish with a maximum flame-spread rating of 25 for corridors and occupancies referred to in Sentences 3.1.13.6.(1) and (4).
Exceptions: 
except for light diffusers and lenses, as stated in Sentence 3.1.13.4.(1).
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A, except buildings that are sprinklered throughout.
Top of Page
Intent
Intent 1: 
To limit the probability that interior ceiling finishes that have an inappropriately high flame-spread property will be used in certain building locations, which could lead to the spread of fire across the exposed surfaces of the finishes, which could lead to harm to persons.
Intent 2: 
To exempt interior ceiling finishes used in certain locations from the application of Sentence 3.1.13.2.(1), which would otherwise permit higher flame-spread ratings, on the basis that a lower flame-spread rating is needed in these locations to protect persons during evacuation.