Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.1.13.7.(4)
+
Application
Application 1: 
Doors serving an exit stairway, a vestibule to an exit stairway, a lobby described in Sentence 3.4.4.2.(2), or a corridor not within a suite, where:
  • the door has a flame-spread rating not more than 200,
  • the door has a smoke developed classification not more than 300, and
  • the aggregate area of all doors is not more than 10% of the area of the wall in which they are located.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A that are regulated by the provisions of Subsection 3.2.6.
Top of Page
Intent
Intent 1: 
To exempt doors in certain locations in high buildings from the application of Sentence 3.1.13.7.(1) and Article 3.1.13.2., which would otherwise require lower flame-spread ratings and smoke development classifications, if certain conditions are met, on the basis that these doors will not significantly contribute to smoke development or flame spread.