Warning This information has been archived because it is outdated and no longer relevant.

Archived Content

Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.1.14.1.(1)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Fire spread test criteria for fire-retardant treated wood roof system used to comply with the requirements of Subsection 3.2.2., in buildings described in Sentence 1.3.3.2.(1) of Division A.
The sentences in Subsection 3.2.2. that relate to this provision are: 3.2.2.25.(2), 3.2.2.32.(2), 3.2.2.53.(2), 3.2.2.59.(2), 3.2.2.69.(2) and 3.2.2.76.(2).
Top of Page
Intent
Intent 1: 
To limit the probability that inappropriate test criteria will be used for the testing of certain roof deck assemblies, which could lead to the spread of fire under the assembly, which could lead to the spread of fire to occupied parts of the building, which could lead to harm to persons.
Top of Page