Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.2.3.1.(5)
OP3
ObjectiveOP3 Protection of Adjacent Buildings from Fire
Attribution
Application
Application 1: 
Calculating the limiting distance, where a building has any storey that is not sprinklered and firefighting facilities cannot reach the building within 10 min of the alarm being received, in buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: 
This also applies to minimum clearances [limiting distances] of tents and air-supported structures to other structures, as stated in Sentence 3.1.6.3.(1).
Top of Page
Intent
Intent 1: 
To limit the probability of the spread of fire from the building to an adjacent building during the time required for emergency responders to perform their duties, which could lead to damage to adjacent buildings.