Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.2.3.15.(1)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Location of skylights in a roof [minimum distance to an exposed wall], where:
  • a wall in a building is exposed to a fire hazard from an adjoining roof of a separate fire compartment that is not sprinklered in the same building, and
  • the exposed wall contains windows within 3 storeys vertically and 5 m horizontally of the roof.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A.
Exceptions: 
except as exempted in Sentence 3.2.3.19.(4), which applies to walkways of noncombustible construction used only as pedestrian thoroughfares.
Top of Page
Intent
Intent 1: 
To limit the probability of the spread of fire from one fire compartment to another fire compartment through windows above the roof of the fire compartment of origin, which could lead to harm to persons in the fire compartment not originally involved in the fire.