Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.4.2.(3) | Application | Intent |
OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Design and installation of fire alarm systems, where
a fire alarm system is required in any portion of a building.
This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A in which fire alarm systems are
installed.
Application 2: This also applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9] in which fire alarm systems are installed, as stated in Sentence 9.10.18.6.(1).
Exceptions:
except as exempted in Sentence 3.2.4.2.(4), which applies
to a building not more than 3 storeys in building height, in which a vertical fire
separation having a fire-resistance rating of
not less than 1 h separates portions of the building from
the remainder of the building as if it were a separate building.
|
Top of Page | |
Intent | Intent 1: To limit the probability that persons in one portion of
a building will not be promptly notified of a fire situation involving another
portion of the building, which could lead to delays in evacuation or moving
to a safe place, which could lead to harm to persons. |