Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.4.4.(3) | Application | Intent |
OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Operation of zone coded 2 stage fire alarm systems
[that have multiple zones], as stated in Article 3.2.4.3.
This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A in which fire alarm systems are
installed.
Application 2: This also applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9] in which fire alarm systems are installed, as stated in Sentence 9.10.18.6.(1). |
Top of Page | |
Intent | Intent 1: To clarify that the operation of 2 stage fire alarm systems
referred to in Sentence 3.2.4.4.(2) may be zone coded under certain
conditions. Intent 2: To limit the probability that a person in charge of fire
safety and emergency response will be unable to ascertain the location of
actuation of an alert signal without the need to respond to an annunciation
panel and without delay, which could lead to directing evacuation of persons
into a hazardous area, which could lead to harm to persons. |
Top of Page |