Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.4.4.(4) | Application | Intent |
OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Operation of 2 stage fire alarm systems [that have
multiple zones], as stated in Article 3.2.4.3., and that are permitted
to be zone coded in Sentence 3.2.4.4.(3). This
applies to buildings described in Sentence 1.3.3.2.(1) of Division A in which fire alarm systems are installed.
Application 2: This also applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9] in which fire alarm systems are installed, as stated in Sentence 9.10.18.6.(1). |
Top of Page | |
Intent | Intent 1: To limit the probability that a person in charge of fire
safety and emergency response will be confused concerning the zone in which
an alert signal originated when more than one zone has initiated an alert
signal, which could lead to directing the evacuation of persons into a hazardous
area, which could lead to harm to persons. |