Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.2.4.4.(4)
OS1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Operation of 2 stage fire alarm systems [that have multiple zones], as stated in Article 3.2.4.3., and that are permitted to be zone coded in Sentence 3.2.4.4.(3).
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A in which fire alarm systems are installed.
Application 2: 
This also applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9] in which fire alarm systems are installed, as stated in Sentence 9.10.18.6.(1).
Top of Page
Intent
Intent 1: 
To limit the probability that a person in charge of fire safety and emergency response will be confused concerning the zone in which an alert signal originated when more than one zone has initiated an alert signal, which could lead to directing the evacuation of persons into a hazardous area, which could lead to harm to persons.