Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.4.14.(1) | Application | Intent |
OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Installation and operation of smoke
detectors in elevator lobbies on the recall level, in buildings having
elevators that serve storeys above the first
storey and that are equipped with an automatic emergency recall feature.
Exceptions:
except as exempted in Sentence 3.2.4.14.(3), which applies
when the floor area containing the recall level
is sprinklered throughout.
This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A.
Application 2: This also applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9] in which fire alarm systems are installed, as stated in Sentence 9.10.18.6.(1). |
Top of Page | |
Intent | Intent 1: To limit the probability that elevators will be recalled
to a floor level involved in a fire, which could lead to harm to persons in
the elevators. |