Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.2.4.14.(2)
OS1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Smoke detectors required by Sentence 3.2.4.14.(1) in elevator lobbies on the recall level, in buildings having elevators that serve storeys above the first storey and that are equipped with an automatic emergency recall feature.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: 
This also applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9] in which fire alarm systems are installed, as stated in Sentence 9.10.18.6.(1).
Top of Page
Intent
Intent 1: 
To limit the probability that persons will not be promptly notified of a fire involving the elevator recall level, which could lead to delays in evacuation or moving to a safe place, which could lead to harm to persons.