Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.4.16.(4) | Application | Intent |
OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Installation of manual stations near doorways leading
from shared interior corridors to the exterior in:
This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A in which fire alarm systems are
installed.
Application 2: This also applies to sprinklered buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9] in which fire alarm systems are
installed, as stated in Sentence 9.10.18.6.(1). |
Top of Page | |
Intent | Intent 1: To limit the probability of delays in the manual activation
of the fire alarm system by a person who is aware of a fire, which could lead
to other persons not being promptly notified of a fire situation, which could
lead to delays in evacuation or moving to a safe place, which could lead to
harm to persons. |