Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.4.18.(5) | Application | Intent |
OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Minimum sound pressure level in sleeping rooms from
fire alarm audible signal devices [forming part of a fire alarm system], where
any intervening doors between the devices and the sleeping rooms are closed.
This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A that are of residential
occupancy in which fire alarm systems are installed.
Application 2: This also applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9] in which fire alarm systems are installed, as stated in Sentence 9.10.18.6.(1). |
Top of Page | |
Intent | Intent 1: To limit the probability that a person in a residential
sleeping room will not be promptly notified of a fire situation and awakened
from sleep, which could lead to delays in evacuation or moving to a safe place,
which could lead to harm to persons. |
Top of Page |