Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.2.4.19.(1)
OS1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Visibility of visual signal devices [forming part of a fire alarm system] required by Sentences 3.2.4.17.(4) and 3.2.4.18.(7) and (8):
  • in buildings or portions of buildings intended for use primarily by persons with hearing impairment,
  • where:
    • the ambient noise level is more than 87 dBA, or
    • the occupants of the floor area use ear protective devices, are located within an audiometric booth or are located within sound insulating enclosures, and
  • in assembly occupancies in which music and other sounds associated with performances could exceed 100 dBA.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A in which fire alarm systems are installed.
Application 2: 
This also applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9] in which fire alarm systems are installed, as stated in Sentence 9.10.18.6.(1).
Top of Page
Intent
Intent 1: 
To limit the probability that persons relying on visual information to warn them of an emergency situation will not be promptly notified of a fire situation, which could lead to delays in evacuation or moving to a safe place, which could lead to harm to persons.