Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.5.10.(5) | Application | Intent |
+ |
Application | Application 1: Installation of 64 mm diam standpipe
hose connections in buildings that are not more
than 25 m high, measured between grade and
the ceiling level of the top storey and in which an
automatic sprinkler system is not installed. This applies
to buildings described in Sentence 1.3.3.2.(1) of Division A in which standpipe systems are installed.
Application 2: This also applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9], as stated in Sentence 9.10.1.2.(8). |
Top of Page | |
Intent | Intent 1: To supersede the requirements of the standard referenced
in Sentences 3.2.5.9.(1) and 3.2.5.10.(4) and
not require hose connections for 64 mm diam hose in buildings
that are limited in height [and not sprinklered], on the basis that the water
supply for such smaller buildings is considered adequate with the provision
of 38 mm hose stations [see Sentence 3.2.5.11.(1)].
|