Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.2.5.10.(5)
+
Application
Application 1: 
Installation of 64 mm diam standpipe hose connections in buildings that are not more than 25 m high, measured between grade and the ceiling level of the top storey and in which an automatic sprinkler system is not installed.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A in which standpipe systems are installed.
Application 2: 
This also applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], as stated in Sentence 9.10.1.2.(8).
Top of Page
Intent
Intent 1: 
To supersede the requirements of the standard referenced in Sentences 3.2.5.9.(1) and 3.2.5.10.(4) and not require hose connections for 64 mm diam hose in buildings that are limited in height [and not sprinklered], on the basis that the water supply for such smaller buildings is considered adequate with the provision of 38 mm hose stations [see Sentence 3.2.5.11.(1)].