Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.5.11.(1) | Application | Intent |
OS1 | OP1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Installation of hose stations for 38 mm diam
hose in buildings that are not sprinklered throughout.
This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A in which standpipe systems are
installed.
Application 2: This also applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9], as stated in Sentence 9.10.1.2.(8).
Exceptions:
except as exempted in Sentence 3.2.5.11.(2), which applies
to a floor area that is sprinklered throughout.
|
Top of Page | |
Intent | Intent 1: To supersede the requirements of the standard referenced
in Sentence 3.2.5.9.(1) and require hose stations for 38 mm diam
hose in buildings that are not sprinklered, to limit the probability that
the water supply to floor areas for firefighting will be inadequate, which
could lead to fire emergency response operations being ineffective, which
could lead to the spread of fire to other parts of the building, which could
lead to harm to persons. |