Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.2.5.11.(3)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Location of hose stations [for 38 mm diam hose] in floor areas in buildings and floor areas that are not sprinklered throughout.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A in which standpipe systems are installed.
Application 2: 
This also applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], as stated in Sentence 9.10.1.2.(8).
Top of Page
Intent
Intent 1: 
To supersede the requirements of the standard referenced in Sentence 3.2.5.9.(1) and require hose stations [for 38 mm diam hose] in certain locations in floor areas, to limit the probability of delays in accessing the water supply to floor areas for firefighting, which could lead to fire emergency response operations being delayed, which could lead to the spread of fire to other parts of the building, which could lead to harm to persons.