Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.5.12.(1) | Application | Intent |
OS1 | OP1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Electrical supervision of valves controlling water
supplies in a standpipe system where a fire alarm system in a building is
required to have an annunciator by Sentence 3.2.4.8.(1).
Exceptions:
except for hose valves.
This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A in which standpipe systems are
installed.
Application 2: This also applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9], as stated in Sentence 9.10.1.2.(8). |
Top of Page | |
Intent | Intent 1: To supersede the requirements of the standard referenced
in Sentence 3.2.5.9.(1) and require electrical supervision of valves
controlling water supplies in a standpipe system, to limit the probability
that the closing of valves that are intended to be normally open, or the opening
of valves that are intended to be normally closed, will go unnoticed, which
could lead to an inadequate water supply to the standpipe system in a fire
situation, which could lead to the fire not being suppressed or controlled,
which could lead to the spread of fire to other parts of the building, which
could lead to harm to persons. |