Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.2.5.13.(4)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Water supply for automatic sprinkler systems where:
  • a building contains fewer than 9 sprinklers, and
  • the required flow for the sprinklers can be met by the domestic system.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A in which automatic sprinkler systems are installed.
Application 2: 
This also applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9] in which automatic sprinkler systems are installed, as stated in Sentence 9.10.1.2.(8).
Top of Page
Intent
Intent 1: 
To exempt small-sized sprinkler systems from the requirements of Sentence 3.2.5.13.(1) and permit the water supply to the sprinkler system to be supplied from the domestic water system, if the domestic supply will provide the required flow for the sprinklers. This is to limit the probability that the sprinkler system will not have an adequate water supply in a fire situation, which could lead to a fire not being suppressed or controlled, which could lead to the spread of fire to other parts of the building, which could lead to harm to persons.