Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.5.15.(2) | Application | Intent |
OS1 | OP1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Waterflow detecting devices for an automatic sprinkler
system in a service space referred to in Sentence 3.2.1.1.(8), where flooring for access within the service
space is other than catwalks [i.e. service space that
could be used for purposes other than access to equipment for maintenance
and that has a floor system on which the workers can walk and store quantities
of supplies]. This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A in which automatic sprinkler systems
are installed.
Application 2: This also applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9] in which automatic sprinkler systems are installed, as stated in Sentence 9.10.1.2.(8). |
Top of Page | |
Intent | Intent 1: To limit the probability of delays in locating the area
of fire origin, which could lead to fire emergency response operations being
delayed or inefficient, which could lead to the spread of fire to other parts
of the building, which could lead to harm to persons. |
Top of Page |