Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.5.15.(3) | Application | Intent |
OS1 | OP1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Connection to fire alarm systems of waterflow detecting
devices for an automatic sprinkler system in a service
space referred to in Sentence 3.2.1.1.(8), where flooring for
access within the service space is other than
catwalks [i.e. service space that could be used
for purposes other than access to equipment for maintenance and that has a
floor system on which the workers can walk and store quantities of supplies].
This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A in which automatic sprinkler systems
are installed.
Application 2: This also applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9] in which automatic sprinkler systems are installed, as stated in Sentence 9.10.1.2.(8). |
Top of Page | |
Intent | Intent 1: To limit the probability that persons will not be notified
of a fire situation, which could lead to delays in evacuation or moving to
a safe place, which could lead to harm to persons. Intent 2: To limit the probability of delays in locating the area
of fire origin, which could lead to fire emergency response operations being
delayed or inefficient, which could lead to:
|
Top of Page |