Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.6.5.(3) | Application | Intent |
OS1 | OP1 |
Objective | OP1 Fire Protection of the Building |
Attribution | |
Application | Application 1: Protection of elevators for use by firefighters.
This applies to high buildings, as defined
in Sentence 3.2.6.1.(1):
Application 2: Clauses 3.2.6.5.(3)(b) and (c) also apply to elevators serving floor areas above or below the first
storey that are not sprinklered throughout
and that have a barrier-free path of travel,
as stated in Clause 3.3.1.7.(1)(a). |
Top of Page | |
Intent | Intent 1: To limit the probability of direct exposure of the elevator
door interlock mechanism to fire, which could lead to the failure of the interlock
mechanism and the opening or partial opening of the elevator doors during
the time required for emergency responders to perform their duties, which
could lead to the failure of the elevator operating mechanism, which could
lead to the elevators not operating as intended, which could lead to delays
or inefficiencies in fire emergency response operations, which could lead
to the spread of fire to other parts of the building, which could lead to
damage to the building. |