Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.2.6.9.(1)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Protection of electrical conductors that:
  • are installed in service spaces containing other combustible material, and
  • are used in connection with fire alarm systems and emergency equipment described in Articles 3.2.6.2. to 3.2.6.8.
This applies to high buildings, as defined in Sentence 3.2.6.1.(1):
Top of Page
Intent
Intent 1: 
To limit the probability that electrical conductors will prematurely fail when exposed to fire, which could lead to fire alarm systems and emergency equipment not properly operating in the fire situation, which could lead to:
  • fire emergency response operations being delayed or ineffective, which could lead to:
    • delays in evacuation or moving to a safe place, which could lead to harm to persons, and
    • the spread of fire to other parts of the building, which could lead to harm to persons,
  • persons not being promptly notified of the fire situation, which could lead to delays in evacuation or moving to a safe place, which could lead to harm to persons, and
  • the buildup of smoke in exit stairs or floor areas, which could lead to:
    • delays or inefficiencies in fire suppression operations, which could lead to the spread of fire, which could lead to harm to persons, including emergency responders, and
    • delays in evacuation or moving to a safe place, which could lead to harm to persons.