Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.2.7.9.(3)
+
Application
Application 1: 
Design, with respect to the minimum duration of the simultaneous operation under a full load of all elevators for firefighters plus one additional elevator, of emergency generator power supplies for elevators required by Clause 3.2.7.9.(1)(a):
This applies where the time to recall all elevators under emergency power supply is not more than 5 min, each from its most remote storey:
  • to the storey containing the entrance for firefighter access referred to in Articles 3.2.5.4. and 3.2.5.5., or
  • to a transfer lobby.
Top of Page
Intent
Intent 1: 
To exempt, from the application of Sentence 3.2.7.9.(2), buildings in which all elevators can be recalled to a reference level within a certain period of time, on the basis that the elevators can be returned before the time that the firefighters' elevator will be required for use.