Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.2.8.2.(5)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Openings for escalators and inclined moving walks, where:
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: 
This also applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], where there are:
  • openings through floors that are not protected by shafts or closures, as stated in Sentence 9.10.1.2.(6), or
  • interconnected floor spaces, as stated in Sentence 9.10.9.5.(1).
Top of Page
Intent
Intent 1: 
To exempt openings for escalators and inclined moving walks from the requirements of Articles 3.2.8.3. to 3.2.8.9., which would otherwise require certain fire protection measures, if:
  • the size of the openings is limited,
  • the building is sprinklered throughout, and
  • the interconnected floor space contains only certain major occupancies.
This is to limit the probability that:
  • large openings will permit the spread of fire to other parts of the building,
  • a fire will not be controlled or suppressed, which could lead to the spread of fire through the openings, and
  • fire hazards [from the type of occupancy] will not be minimized, which could lead to the start and spread of fire through the openings.
This is to limit the probability of harm to persons.