This information has been archived because it is outdated and no longer relevant.
Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.8.4.(1) | Application | Intent |
OS1 | OP1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Sprinkler protection of buildings described
in Sentence 1.3.3.2.(1) of Division A that contain an interconnected
floor space. This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A that contain portions of a floor area or mezzanines that
do not terminate at an exterior wall, a firewall or
a vertical shaft, and are required by Clause 3.2.8.1.(1)(b) to be protected
in conformance with Articles 3.2.8.3. to 3.2.8.9.
Application 2: This also applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9], where there are:
Exceptions:
except as exempted in:
|
Top of Page | |
Intent | Intent 1: To limit the probability that a fire will not be controlled
or suppressed, which could lead to the spread of fire within an interconnected
floor space, which could lead to harm to persons. |
Top of Page |