Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.3.2.12.(2)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Fire separations required by Sentence 3.3.2.12.(1) that separate library book storage rooms from the remainder of the building, where the library book storage room is sprinklered.
This applies to library book storage rooms that are not normally accessible to the public, and:
  • are more than 250 m2 in area, or
  • contain book stacks that:
    • are more than 10 m high, or
    • penetrate more than one floor assembly.
This applies to assembly occupancies in buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: 
This also applies to:
  • tents and air-supported structures, as stated in Sentences 3.1.6.1.(1) and 9.10.1.2.(1), and
  • buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], as stated in Sentence 9.10.1.2.(2).
Top of Page
Intent
Intent 1: 
To exempt book storage rooms from the application of Sentence 3.3.2.12.(1) by waiving the requirement for a fire separation on the basis that the room is sprinklered.
This is to limit the probability that fire will spread from the book storage room to other parts of the building, which could lead to harm to persons in other parts of the building.