Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.3.3.5.(7)
OS1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Maximum travel distance from any point within each fire compartment referred to in Sentence 3.3.3.5.(2) to a door to an adjoining fire compartment, in floor areas containing patients' sleeping rooms in a hospital or nursing home.
This applies to care or detention occupancy in buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: 
This also applies to tents and air-supported structures, as stated in Sentences 3.1.6.1.(1) and 9.10.1.2.(1).
Exceptions: 
except as stated in:
Top of Page
Intent
Intent 1: 
To limit the probability of excessive travel distances to a door to an adjoining fire compartment, which could lead to delays in moving patients to the adjoining fire compartment in a fire situation, which could lead to harm to persons.