Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.3.4.3.(3) | Application | Intent |
+ |
Application | Application 1: Minimum fire-resistance rating of fire separations that separate storage rooms referred
to in Sentence 3.3.4.3.(1) from the remainder of the building,
where the fire-resistance rating required by Subsection 3.2.2. is permitted to be less than 1h for:
This applies to storage rooms provided
for the use of tenants in a residential occupancy within
a floor area, but not contained within a suite, in buildings described
in Sentence 1.3.3.2.(1) of Division A.
Application 2: This also applies to tents and air-supported
structures, as stated in Sentences 3.1.6.1.(1) and 9.10.1.2.(1).
Exceptions:
except as stated in:
|
Top of Page | |
Intent | Intent 1: To supersede the requirements of Sentence 3.3.4.3.(2) and
permit a lower minimum fire-resistance rating on the basis that the rating
of the separation need not be any more than that of the other assemblies that
enclose the room. |