Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.3.5.3.(3) | Application | Intent |
OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Vapour-tight separations of basements and
rooms containing building services from the remainder
of the building, in buildings where:
This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A.
Application 2: This also applies to:
Exceptions:
except as stated in:
|
Top of Page | |
Intent | Intent 1: To limit the probability that explosive air-vapour mixtures
or dusts will migrate into basements or service rooms from areas of the building
involved with the hazardous products, which could lead to the accumulation
of the mixtures or dusts in sufficient quantity to form an ignitable mixture,
which could lead to the ignition of the mixtures or dusts from a nearby ignition
source, which could lead to harm to persons. |