Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.3.5.8.(2) | Application | Intent |
OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Location of facilities for the dispensing of fuel
having a flash point below 37.8°C inside buildings.
Exceptions:
except for canopies that are open on not less than 75% of their
perimeter.
This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A.
Application 2: This also applies to:
Exceptions:
except as stated in:
|
Top of Page | |
Intent | Intent 1: To limit the probability that vapours will migrate into
other areas of a building, which could lead to the accumulation of the vapours
in sufficient quantity to form an ignitable mixture, which could lead to the
ignition of the vapours from a nearby ignition source, which could lead to
harm to persons. Intent 2: To limit the probability that vapours will accumulate in
sufficient quantity to form an ignitable mixture, which could lead to the
ignition of the vapours from a nearby ignition source, which could lead to
harm to persons. Intent 3: To exempt canopies that are open on not less than 75% of
their perimeter from the requirements of Sentence 3.3.5.8.(2) and permit
fuel-dispensing operations inside a building, on the basis that the building
design provides direct ventilation to the outdoors, thus limiting the probability
that vapours will accumulate to ignitable concentrations or migrate to other
parts of the building. |