Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.4.1.2.(2) | Application | Intent |
OS3 |
Objective | OS3 Safety in Use |
Attribution | |
Application | Application 1:
This applies to floor areas that are
intended for occupancy, including mezzanines as
stated in Sentence 3.4.2.2.(1), in buildings described
in Sentence 1.3.3.2.(1) of Division A.
Application 2: This also applies to tents and air-supported
structures, as stated in Sentences 3.1.6.1.(1) and 9.10.1.2.(1).
Exceptions:
except as stated in:
|
Top of Page | |
Intent | Intent 1: To exempt multiple exits from the requirement of Sentence 3.4.1.2.(1), which requires that all exits be separate, if measures
are taken to limit the cumulative capacity of the converging exits.
This is to limit the probability that an excessive portion of the
required exiting capacity will consist of converging exits, which could lead
to insufficient width in other exits to permit efficient egress in an emergency
situation if the converged exit becomes obstructed or inaccessible, which
could lead to delays in the evacuation or movement of persons to a safe place,
which could lead to harm to persons.
Intent 2: To direct Code users to Sentence 3.4.3.1.(2).
|