Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.4.3.2.(4)
+
Application
Application 1: 
Required exit width of exits serving 2 or more floor areas located one above the other.
This applies to exits serving floor areas that are intended for occupancy, including mezzanines as stated in Sentence 3.4.2.2.(1), in buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: 
This also applies to:
Exceptions: 
except as stated in:
Top of Page
Intent
Intent 1: 
To exempt an exit stair from the application of Sentence 3.4.3.1.(2) for converging exits, which would otherwise require the exit width to be cumulative, based on the total occupant load of the superimposed storeys served by the exit, on the basis that exits need only be designed for a fire or other untenable conditions occurring on one floor area and the occupants moving from that floor area.