Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.4.4.1.(2)
+
Application
Application 1: 
Maximum fire-resistance rating of fire separations that separate exits from the remainder of the building.
This applies to exits serving floor areas that are intended for occupancy, including mezzanines as stated in Sentence 3.4.2.2.(1), in buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: 
This also applies to tents and air-supported structures, as stated in Sentences 3.1.6.1.(1) and 9.10.1.2.(1).
Top of Page
Intent
Intent 1: 
To supersede the requirements of Sentence 3.4.4.1.(1) in regard to exit enclosures passing through floor assemblies, which are required by Subsection 3.2.2. to have a 3 h fire-resistance rating, which would otherwise require the exit enclosure to have a fire-resistance rating above 2 h, on the basis that the 2 h fire-resistance rating of the fire separation is considered to provide an adequate level of protection.