Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.4.7.6.(1)
OS3
ObjectiveOS3 Safety in Use
Attribution
Application
Application 1: 
Minimum height of guards protecting the open sides of platforms, balconies and stairways forming part of a fire escape referred to in Sentence 3.4.7.1.(2), where:
This applies to fire escapes serving floor areas that are intended for occupancy, including mezzanines as stated in Sentence 3.4.2.2.(1), in buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: 
This also applies to:
  • tents and air-supported structures, as stated in Sentences 3.1.6.1.(1) and 9.10.1.2.(1), and
  • existing buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], as stated in Sentence 9.9.2.1.(2).
Exceptions: 
except as stated in:
  • Sentence 3.1.6.2.(1), which prohibits air-supported structures from being located above the first storey on any building,
  • Sentence 3.1.6.2.(2), which prohibits air-supported structures from being used for classrooms or for Groups B, C, or Group F, Division 1 major occupancies,
  • Sentence 3.1.6.2.(3), which requires air-supported structures to be designed as open floor spaces without interior walls, mezzanines, intermediate floors or similar construction,
  • Sentence 3.3.1.3.(5), which applies to rooftop enclosures,
  • Sentence 3.4.2.2.(2), which applies to mezzanines that:
    • are not required to terminate at a vertical fire separation [see Article 3.2.8.1.],
    • are not intended for an occupant load more than 60,
    • do not exceed the area limits for rooms and suites in Table 3.4.2.2., and
    • have limited travel distances to egress doors or stairs, and
  • Sentence 3.4.2.2.(3), which applies to at least half of the required means of egress from a mezzanine if the mezzanine is not required to terminate at a fire separation as permitted by Sentence 3.2.8.2.(1).
Top of Page
Intent
Intent 1: 
To exempt guards protecting fire escape platforms, balconies and stairways from the requirements of Sentence 3.4.6.5.(2) and permit a lower minimum guard height, on the basis that the fire escapes will be used infrequently.
This [the minimum guard height] is to limit the probability that:
  • persons using the fire escape will fall over the guard from a higher level to a lower level, which could lead to harm to persons, and
  • the absence of a high guard will inhibit the use of the fire escape during an emergency situation, which could lead to delays in the evacuation or movement of persons to a safe place, which could lead to harm to persons.
Top of Page