Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.5.3.3.(2)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Fire separation that separates a room containing elevator machinery from the elevator hoistway that it serves, where the room and the hoistway are separated from all other parts of the building by a fire separation having a fire-resistance rating not less than that required for the vertical service space containing the elevator hoistway.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: 
This also applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], as stated in Sentence 9.10.1.2.(1).
Top of Page
Intent
Intent 1: 
To supersede the requirements of Sentence 3.5.3.3.(1), which would otherwise require a room containing elevator machinery to be separated from the elevator hoistway by a fire separation, and waive such separation if certain conditions are met [the room and the hoistway are separated from all other parts of the building].
This is to limit the probability that:
  • a fire involving the room and hoistway will spread to other parts of the building, which could lead to harm to persons in other parts of the building, and
  • a fire will spread from other parts of the building into the room and hoistway, which could lead to:
    • harm to persons in elevator cars in the hoistway, and
    • the failure of the elevator machinery, which could lead to harm to persons in elevator cars.