Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.6.2.6.(1)
OS1OS3
ObjectiveOS3 Safety in Use
Attribution
[F30-OS3.1] Applies to portion of Code text: “A swing-type door from a service room containing a boiler or incinerator shall swing … inward if the door opens onto a corridor or any room used for an assembly occupancy.”
Application
Application 1: 
Direction of swing of swing-type doors from a service room containing a boiler or incinerator, where the door opens onto a corridor or any room used for an assembly occupancy.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A.
Top of Page
Intent
Intent 1: 
To supersede the requirement for an outward swinging door in the first part of Sentence 3.6.2.6.(1) and require the door to swing inwards in situations where there will likely be people on the other side of the door.
This is to limit the probability that a door swinging outwards will hit persons, or lead to persons hitting or bumping into the door, which could lead to harm to persons.