Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.6.2.7.(6) | Application | Intent |
OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Design, with respect to preventing the ambient temperature
from exceeding 40°C, of ventilation systems serving electrical equipment
vaults [referred to in Sentence 3.6.2.7.(1)] required by:
This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A.
Application 2: This also applies to transformer vaults in buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9], as stated in Sentence 9.10.1.2.(1). |
Top of Page | |
Intent | Intent 1: To limit the probability of heat buildup in an electrical
equipment vault, which could lead to the failure of the electrical equipment
in the vault, which could lead to a fire or explosion in the vault, which
could lead to harm to persons in other parts of the building. Intent 2: To direct Code users to Part 6. |