Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.6.2.7.(8) | Application | Intent |
OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Spill control measures for electrical equipment vaults
[referred to in Sentence 3.6.2.7.(1)] required by:
This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A.
Application 2: This also applies to transformer vaults in buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9], as stated in Sentence 9.10.1.2.(1). |
Top of Page | |
Intent | Intent 1: To limit the probability that escaped liquid will spread
outside the vault, which could lead to the ignition of vapour by a nearby
ignition source, which could lead to harm to persons. Intent 2: To limit the probability that ignited liquid from a fire
in the vault will spread outside the vault, which could lead to the spread
of fire to other parts of the building, which could lead to harm to persons.
|
Top of Page |